Logo National Lab GmbH

Intelligent

Recirculating Chillers

 

Recirculating Chillers

ProfiCool Genius PCGE 3150 to PCGE 3650
Cooling capacity 276 kW to 350 kW

Device 6A11

Standard design

 

Technical data:

Model ProfiCool Genius
Net. cooling capacity * at +20 °C / +15 °C
Eff. cooling capacity * at +20 °C / +15 °C
Operating range **
Temperature constancy
Rated coolant flow
Pump type
Pump pressure ***
Tank capacity
Water connection, female
Required flow of cooling air
Starting current
Power input max.
Operating voltage
Weight
Dimensions (W × D × H)
Refrigerant, CFC-free
Catalogue number
 
 
kW :
kW :
°C :
°C :
m³/h :
:
bar :
L :
:
m³/h :
A :
kW :
:
kg :
mm :
:
:
 
PCGE 3150
302.4 / 283.5
294.9 / 276.0
+5 / +25
±1.5
48.8
P3-AP35B
3.5
500
G3"
71400
394
79.0
3/N/PE ~ 400 V 50 Hz
2380
3990 × 1525 × 2170
R407C
GUPCGE3150.01-NEB
 
PCGE 3650
350.4 / 328.5
342.9 / 321.0
+5 / +25
±1.5
56.5
P3-AP35B
3.3
500
G3"
92000
468
89.9
3/N/PE ~ 400 V 50 Hz
2510
3990 × 1525 × 2170
R407C
GUPCGE3650.01-NEB
 
* Net. cooling capacity: the heating current that is removed from the coolant inside the evaporator.
   Eff. cooling capacity: the heating current that the coolant usefully removes.
** Set temperatures < +5 °C and > +25 °C on request.
*** Pump pressure at rated coolant flow.

Additional options and accessories

ProfiCool Genius options / accessories Cat.No.
Pump P7-AP38B instead of P3-AP35B (3/N/PE ~ 400V 50Hz) MPCGE6-P7-AP38B-3650
Pump P8-AP39B instead of P3-AP35B (3/N/PE ~ 400V 50Hz) MPCGE6-P8-AP39B-3650
Continuous-flow system without tank and / or without pump on request
Overflow by-pass valve ZPCGE6-041-3650
4 swivel castors, 2 with breaks ZPCGE5-021-3650
Temperature constancy up to ±0,5 °C on request
Low ambient temperature kit MPCGE7-001-3650
Export version with special voltages / frequencies on request
Flange connection on request

Additional options and accessories . . .

. . . as well as pump alternatives on   ⇒ request

Pump characteristics

Diagramm 6A11

Dimensions and connections

Dimensions 6A11

Download Data sheet 6A11

*.PDF
All rights reserved. Changes without notification © National Lab GmbH 2013